datacenter
Ceiling clearance133 inches
Cross Connect TypesFiber and Copper
Date built1999
Total space5800 sq ft
power and cooling
ChillerN+1 Chiller
Cooling configurationCRAC with Redundant Power
Cooling redundancyN+1
Cooling systemPerimeter CRAC units with raised floor plenum supply in cold aisle/hot aisle configuration
Cooling system capacity120 tons
Floor typeRaised
Generator configuration1 Generator/Building Property
Pre-action dry pipe systemYes
UPS configuration3 UPS (80/160/150kVA) GE & Exide
UPS redundancyN+1
products and services
Remote hands notes24x7x365